Dilan Yıldız is Process and Energy Management Lead Engineer at TÜPRAS Batman refinery. She has worked for TÜPRAS since 2018. Yıldız earned a BS degree in chemical engineering from Yıldız Technical University, and an MS degree in chemical engineering from Istanbul Technical University. She is currently pursuing an MBA at Koç University.
The effects of cooling water parameters on condenser brass tubes
This work is focused on the effect of cooling water parameters on admiralty brass tubes. The effect of high free chlorine on the corrosion rate of brass tubes has been investigated by scanning electron microscopes (SEMs) and eddy current test (ECT) methods and the laboratory results of the cooling water were determined and discussed. Also, the tendency of the feed water scaling indices that is LSI, PSI & RSI was calculated. The results show that a dezincification corrosion mechanism was observed due to the high-level free chlorine on the admiralty brass tube.